Rgds
B.Wills
The other big problem is turn-down ratio. For control loops with flow control valves, we think nothing of using it at 100:1 turn-down ratio. Because of the centrifugal pump, using a VFD limits use to about a 3:1 turn-down ratio. Now, that said, there are a large number of control loops where a 3:1 turn-down ratio is more than adequate during steady-state operation -- these are the 15 percent.
Dick Caro
============================================
Richard H. Caro, CEO
CMC Associates
2 Beth Circle, Acton, MA 01720
Tel: +1.978.635.9449 Mobile: +1.978.764.4728
Fax: +1.978.246.1270
E-mail: RCaro@CMC.us
Web: http://www.CMC.us
============================================
It would not surprise me that only 15 percent (or less) of centrifugal pumps utilize variable speed drives. However, although not designed to run at reduced speed, centrifugal pumps do so quite well... and usually with fewer maintenance problems.
The affinity laws mathematically describe the relationship between pump head, volume and speed. In short, reducing the speed is equivalent to reducing impeller size (in an energy-efficient manner). Impeller curves commonly appear on pump curves and their equivalent speeds can be calculated.
Turndowns of 100:1 may or may not be practical, however centrifugal pumps with variable speed drives will generally operate well in excess of 3:1 turndown, say 20:1 or so, depending upon the hydraulics.
For more information (and the mathematical details), see my book "Variable Speed Drives: Principles and Applications for Energy Cost Savings", available at www.isa.org.
Best Regards,
David W Spitzer 845.623.1830 dwspitzer@aol.com
Jose R Pabon
rpabon@dextonsa.com
Jon
--
Steve Myres, PE
Automation Solutions
(480) 813-1145
You are correct regarding application criteria.
The very first two applications to use the then new NASA patent (eventually to become VFD or VSD) were a total failure. One caused a refinery fire. The other revealed that reducing the original motor size by 50% would have saved an enormous amount of money... w/o the VFD!
All forum contributors, thus far, have lauded the benefits... but what about the hidden costs! Often overlooked are the impact on the electrical system. How often have you heard... harmonics are not a problem! Just add a filter here! Or, an isolating transformer there! Just "tweak" the VFD parameters! Perhaps the cable is too short! Or too long! Or, not the "right" one. How about "start-up" problems! Harmonics? Must be the motor. Maybe, its the utility! Is it 'P'! Perhaps 'Q'. No, its the tech... Uncanny how often the tech or operator is blamed. But, never, I said, never the fault of the engineer! Bring in the PQ team!
How about those "strange" unexplained events. For example, Plant B experiencing electrical problems about the time plant A, 1 mile away, installed a VFD. Then, there's the panel is too hot! The grand-daddy of all... the dreaded "neutral" current phenomena, or power-factor capacitor resonance. A close third... IGBT failure syndrome. Could it be dv/dt? Or is it di/dt? etc, etc. Don't even get me started on software "glitches"! And, I could go on, and on, and...
Reminds me of the car owner that kept adding fuel-saving additives and devics to his car. Finally, he had them removed, because his fuel tank kept overflowing!
Enough of the rant. Too all... have a good life!
Regards, Phil Corso, PE Boca Raton, FL [tal-2@webtv.net] (Epsiconinc@aol.com) {pcorso@itt-tech.edu}
This subject is is covered in my book "Variable Speed Drives: Principles and Applications for Energy Cost Savings" available at www.isa.org. Properly applied... the benefits can be many.
David W Spitzer
dwspitzer@aol.com
845.623.1830
A drive can give you so much more flexibility and information about the state of the process that it's just silly. It's also better for the system IMHO because of smoother changes in pressure.
pros:
1)very accurate flows. the shaft of the motor is normally attached to the pump, if the speed of motor is known, the pumping capacity will be known as well. you can do an open loop flow control without much trouble. using the vfd, the speed of motor is known at all times. a flow meter will not be required in normal cases, you can probably guess-timate the flow by trials.
2)vfd is especially good for low flow rate applications, where the line size is fairly small ~1" (metering pump applications). you would not be able to use a control valve here as the line size is small and you may risk build-ups in the valve. also it is very hard to size flowmeters for low flowrates/small lines.
3) nearly no maintenance as no moving parts are present in a vfd.
4) fairly high linearity in flow vs speed setpoint graph.
cons:
1) the best turndown a vfd can achieve conveniently is around 4:1. beyond that, it is really pushing it and you may need a bigger motor/gear-reducers to achieve 5:1 turndowns or higher.
control valves:
pros:
1) you can shut the valve right up, assuming it is safe to do so.
2) are suitable on boiler applications or other critical applications where the ability for a complete flow stop is required (emergencies)
3)a flow valve's cost varies depending on the fluid flowing thru it. cast iron valves are dead cheap and so are their actuators.
4) suitable for large line sizes ~15"-36" where super accuracy isnt required. example mill-wide water supply etc.
cons:
1)they require annual maintanence and rebuilding.
2)you require a flow meter in all the cases for a successful control of the flow. a magflow tube is expensive and the cost increases with higher line size. oriface plates can be used too but only with water as the fluid.
these are my $0.02.
rahul chander
Do you remember how ecstatic the refinery control potentates were when they discovered (late 60's) that NASA' simple patent for controlling motor speed could, potentially, save lots of money... a fact that the chem boys knew from day one! It was also the main reason EXXON bought Reliance Electric!
Ah, the joy of being old, oops, older!
Regards, Phil Corso, PE Boca Raton, FL [tal-2@webtv.net] (Epsiconinc@aol.com) {pcorso@itt-tech.edu}
I remember that fiasco very well. Exxon thought that VFD would completely replace the need for control valves, and they wanted a piece of that action, so they bought Reliance Electric who actually held the patent. Then the Federal Trade Commission opposed Exxon in court and actually prevented them from exploiting the technology. Exxon allowed Reliance management to do a leveraged buyout a few years later resulting in a huge loss for Exxon.
Reliance had it right....and so did Exxon. Government interference really killed this one. Today VFD is big business, although not where Exxon thought it would be.
Dick Caro
there are several case studies that may be helpful.
John Gierich
Joliet Technologies, L.L.C.
I would post the entire article if it wasn't so long.
Feel free to browse our website. We've got some great information about electric motors, variable frequency drives, and backup generators.
- ABCs of SBCs: Single board computers for embedded control; Lego learning
- Less, more: NEMA cites less confidence; NAM sees more exports of manufactured goods
- Free webinar on Zigbee for embedded systems
- Better together? Ametek, Dresser-Rand, IntervalZero, Rexroth make acquisitions
- You need 2 monitors: This Website will prove it
- Preview: Mitsubishi iQ controls sequence, motion, process, CNC, robotics; has connectivity
- 30 new Rockwell Automation products integrate hardware, software
- Software certified by AT&T: Runs on PDAs, cellphones, enables mobile applications
- Research: HMI supervisory software use increases with service needs
- Process modeling: Spreadsheets support multiphase flow simulation
Patronize our advertisers!