I am developing float Rectifier cum Charger for our Telecom Product. I am supporting two alternate AC utility supply (230V AC 50 Hz) input, out of which only one at a time has to be selected. The load is 6 Amps.
I am concerned about a few aspects :
* What would be the best way of judging the power supply to be selected.
* How to best implement it. ( Contactor etc)
* How about the Earthing issue. ( Vis a vis two different AC Sources)
* MCB in such case should be double Pole or Single Pole (OR Three pole)???
PLease advise.
THANKS
ashokg@cdotp.ernet.in
Ashok Gupta
CDOT
India
You want to have two independant power sources, and be able to select one of them, I suppose this is because one might fail and the operation can continue uninterrupted. Did I get it right, you want DC voltage out of it?
If all this is correct:
Two cases, case one: you want to use some kind of power supply to produce the actual output voltage (probably lower than the input voltage). I would do like this: use two independant power supplies and connect them togheter using a pair of diodes.
Depending on how the actual power supplies are made you might not even need the diodes.
Case two: you more or less just want to rectify the AC line voltage and diretly use it for something. Put an insulation transformer on one of the inputs, reactify each AC voltage
separately and then just connect them to each other.
With either of these methods the currently strongest source is the one feeding the load. If they are equal enough the load will be divided between the two sources (not necesarily 50% each).
Grounding: if you use an insulation transformer on one of the sources you just cut that ground and use the other one.
If what you really want is an AC output, forget about this reply.
/Johan Bengtsson
----------------------------------------
P&L, the Academy of Automation
Box 252, S-281 23 H{ssleholm SWEDEN
Tel: +46 451 49 460, Fax: +46 451 89 833
E-mail: johan.bengtsson@pol.se
Internet: http://www.pol.se/
----------------------------------------
Thanx for the response.
Yes, I want to have two independant AC power sources, and be able to select one of them, Yes, this is because one might fail and the operation can continue uninterrupted. I shall be getting AC volts out of it. (230V AC 50 Hz, 5 Amps max.)
PLease suggest me suitably. I would also like to monitor the voltage of each of these before I could actually connect the power sources to the
load side.
ashokg@cdotp.ernet.in
Ashok Gupta
Research Engineer
C-FITL
CDOT
II Floor
#39, Main Pusa Road
N. Delhi 110 005
thanks
sudarshan.k
synchronising voltage and frequency first. This can even lead to severe damage of the power generating equipment. So without knowing what's behind not my 2c note
Regards Rolf
flow when the contacts are both shut. I've seen the results of that and they aren't pretty.
A better solution, IMHO, if the switchover time is a problem, would be to get the fastest relays available and wire to break before make. I've seen
this work with switchover times of less than 50 ms.
Paul Butchart
Process Control Engineer
Qualitech Steel SBQ, L.L.C.
pbutchart@qualitech-steel.com
1. You have no reason if the power already have gone
2. If it would make any difference it means you make a switchover when you have power from both sources, since they are probably not the same phase you will short circuit both your sources.
/Johan Bengtsson
----------------------------------------
P&L, the Academy of Automation
Box 252, S-281 23 H{ssleholm SWEDEN
Tel: +46 451 49 460, Fax: +46 451 89 833
E-mail: johan.bengtsson@pol.se
Internet: http://www.pol.se/
----------------------------------------
- Temperature, relative humidity sensors pair with wireless network
- Intrinsically safe accelerometer expands line of hazardous area sensors
- Power: Digital converter growth; fuses, harvesting, supplies, transformers, UPS
- Terminal blocks: 125 A, 1,000 V, 15 mm pitch; 100 kA short circuit current rating
- Industrial Ethernet: High density I/O, no-tool RJ45 Ethernet connector, extenders
- RFID: Tag for boxes or polymeric containers, future trends, training
- Enclose, protect: 2 plastic enclosures; device measures heat, airflow
- Control Engineering System Integrators Hall of Fame
- User group meetings: Trade show, conference, motivational seminar, and party, all in one
- Process safety system: Flexible platform designed to increase plant profitability
Users of this site are benefiting from open source technologies, including PHP, PostgreSQL and Apache. Be happy.
Patronize our advertisers!