Topic: Power generation equipment control.
from the Controls department...
Generator Synchronization
Originally posted by Ekemini on 3 October, 2012 - 8:27 am
Having difficulties to synchronize the Gas Turbine Generator (Frame 9, MK VI) with the grid.
New Replies:
Yes. I think the issue is with the ELIN processor because the Wiring from the module to MK VI is...
> Happy troubleshooting and update us the progress. Good Luck Thanks for your directives. The...
The Vdc split is okay. The L3-complete sequence is also okay as the GT always attains FSNL...
The protective relay has been reset but we can't check for the "close" signal because the...
All other modules are working correctly and with the correct indication too. The Excitation...
Actually, its from the toolbox that i noticed L27Bn was 0 and not 1, hence blocking the Auto-Synch...
Yes. There was maintenance carried out as a result of cable earth fault. The fault has been...
Select Page: 1
 
 

Your use of this site is subject to the terms and conditions set forth under Legal Notices and the Privacy Policy. Please read those terms and conditions carefully. Subject to the rights expressly reserved to others under Legal Notices, the content of this site and the compilation thereof is © 1999-2013 Nerds in Control, LLC. All rights reserved.