Multi protocol Scada

B

Thread Starter

Brokenwire

I need to implement a SCADA system and I chose Wonderware from In touch. I chose too the DNP LAN as the driver that will provide connection between SCADA and the RTU device. All the system mounted over a Industrial Multiport computer Windows based.

But on other hand, I want to take advantage of that system for built a open DB for others applications take the data they need. For example, Manteinance programs for engineers.

The question is, Since I´ll have a DNP master and one or more others drives slaves:
Can I do that without drivers conflicts?
Where is the key? In the Operating System?

Thanks
 
I would suggest that if your DNP Master is a PC then log you data to MS Access Database using the Wonderware Application. That way the different departments has access information they need for reports, etc....
 
M
We assume that you're using DNP3 DDE Server as the protocol I/O driver, therefore you could just connect your multiple DDE Client to this DDE Server.

There will be no conflict at all.

The key is on the utilized protocol I/O driver.

M. Harisman
www.integrateknik.com