Pressure cv vs. pressure regulator

H

Thread Starter

hosseini

Please explain to me the difference between pneumatic control valve and pressure regulator valve, especially in the control actuation object.
 
A pneumatic control valve (also electronic, or digital fieldbus) has an input (setpoint) the desired valve position from a controller output. This value is used to regulate the pressure applied to the valve's pneumatic motor, typically using a source of high pressure instrument air, that opposes a spring and may be either air-to-open or air-to-close, depending on the desired fail-safe direction. The positioning action is proportional to the valve setpoint signal.

A pressure regulator is a somewhat similar device with a fixed setpoint used to keep a line pressure (such as steam or air) at a constant value. The control action is local and usually does not depend on a source of instrument air. In a regulator, the process fluid usually opposes the spring force to move the valve position. Use of a regulator for other than steam or air is unusual.

Dick Caro
===========================================
Richard H. Caro, Certified Automation Professional, CEO, CMC Associates,
2 Beth Circle, Acton, MA 01720
Tel: +1.978.635.9449 Mobile: +.978.764.4728
Fax: +1.978.246.1270
E-mail: [email protected]
Web: http://www.CMC.us
Buy my books:
http://www.isa.org/books
Automation Network Selection
Wireless Networks for Industrial Automation
http://www.spitzerandboyes.com/Product/fbus.htm
The Consumer's Guide to Fieldbus Network Equipment for Process Control
Buy this book and save 50% or more on your next control system!!!
===========================================
 