CS3000 error message

B

Thread Starter

Bill King

I am attempting to change the switch label table in CS3000. I continue to encounter this error:

FindDifference(): RegisterInstLabelEDFWithRDB.

Has anyone encountered this problem? Any help would be greatly appreciated.
 
Hi,

You aren't trying to write to the systems reserved switches?

These can't be changed and my cause such an error.
 
Thanks, Darren.

The problem I was encountering was due to a "mismatch" in my AN table. The way I resolved the problem was to export both the AN and SW table, then I deleted all entries from both tables. After this was completed I made the modifications I needed to make to InstLable table. This table was downloaded. I then reloaded the tables. I downloaded the project without errors.
 
Top