N
Dear All,
I am looking for some information on the DP transmitter connection for boiler drum level measurement. I am basically looking for if the steam and water side of the drum is connected to the high or low end of the DP transmitter and the reason.
I looked at various postings in the Control.com. I found the followings thread little bit useful but not so clear.
http://www.control.com/thread/1026228727#1342623072
This thread tell to connect the steam side to the high end of the transmitter and water side to the lower end of the transmitter.
I also looked at one of the article in EMERSON website: http://www2.emersonprocess.com/siteadmincenter/PM Rosemount Documents/00840-0100-4360.pdf
This article shows to connect the Low end of the transmitter to the steam side and high end of the transmitter to water side .This is also confusing.This article says the DP is maximum when the level is lowest and DP is minimum when the level is highest. It again says when the level is minimum the transmitter out will be 4 ma. So it is confusing . At the minimum level if the DP will be highest how the transmitter output 4 ma.This is really confusing.
Both the above information does not tell the reason why and which side of the drum (Water or Steam) needs to be connected to the high or low end of the transmitter. So I need all of your suggestion to clarify this.We are using Rosemount DP transmitter for drum level measurement. I have the following questions:
1. The steam and water side of the drum will be connected to High or Low end of the transmitter and why?
2. The DP will increase or decrease with increasing and decreasing level and why?
3. When the level is highest the DP transmitter output will be 20 ma or 4 ma?
4. Why to use the condensing pot in steam side tapping point?
Regards
Narayan
I am looking for some information on the DP transmitter connection for boiler drum level measurement. I am basically looking for if the steam and water side of the drum is connected to the high or low end of the DP transmitter and the reason.
I looked at various postings in the Control.com. I found the followings thread little bit useful but not so clear.
http://www.control.com/thread/1026228727#1342623072
This thread tell to connect the steam side to the high end of the transmitter and water side to the lower end of the transmitter.
I also looked at one of the article in EMERSON website: http://www2.emersonprocess.com/siteadmincenter/PM Rosemount Documents/00840-0100-4360.pdf
This article shows to connect the Low end of the transmitter to the steam side and high end of the transmitter to water side .This is also confusing.This article says the DP is maximum when the level is lowest and DP is minimum when the level is highest. It again says when the level is minimum the transmitter out will be 4 ma. So it is confusing . At the minimum level if the DP will be highest how the transmitter output 4 ma.This is really confusing.
Both the above information does not tell the reason why and which side of the drum (Water or Steam) needs to be connected to the high or low end of the transmitter. So I need all of your suggestion to clarify this.We are using Rosemount DP transmitter for drum level measurement. I have the following questions:
1. The steam and water side of the drum will be connected to High or Low end of the transmitter and why?
2. The DP will increase or decrease with increasing and decreasing level and why?
3. When the level is highest the DP transmitter output will be 20 ma or 4 ma?
4. Why to use the condensing pot in steam side tapping point?
Regards
Narayan
